beautypg.com

Figure 2-3. hsp series rear panel connections, Table 2-1. i/o connector pin assignments, Hsp series rear panel connections -2 – KEPCO HSP Series Operator Manual User Manual

Page 16: I/o connector pin assignments -2, 3 and, Ble 2-1

background image

2-2

HSPSERIES OPR 050614

FIGURE 2-3. HSP SERIES REAR PANEL CONNECTIONS

TABLE 2-1. I/O CONNECTOR PIN ASSIGNMENTS

PIN NO.

NAME

DESCRIPTION OF FUNCTION

REF. PAR.

1

X

NO CONNECTION

2

X

NO CONNECTION

3

FFS-1

FAN STATUS - NORMALLY CLOSED CONTACT

3.14

4

ACS-C

SOURCE POWER STATUS - COMMON CONTACT

3.14

5

ACS-2

SOURCE POWER STATUS - NORMALLY CLOSED CONTACT

3.14

6

X

NO CONNECTION

(1)

7

RC2

REMOTE INHIBIT - NORMALLY LOW INPUT

(2)

3.12

8

RC1

REMOTE INHIBIT - NORMALLY HIGH INPUT

(2)

3.12

9

X

NO CONNECTION

(1)

10

X

NO CONNECTION

11

OTS-C

OVERTEMP STATUS - COMMON CONTACT

3.14

12

PSS-C

OUTPUT STATUS - COMMON CONTACT

3.14

13

PSS-2

OUTPUT STATUS - NORMALLY CLOSED CONTACT

3.14

14

ISHARE

LOAD SHARE SIGNAL BUS (0-5.5V)

(3)

2.7.6

15

IPROG

ANALOG PROGRAMMING INPUT - CURRENT (0-10V)

(3)

3.5

16

X

NO CONNECTION

17

VRP-1

RESISTIVE PROGRAMMING INPUT (0-10K)

3.3

18

VPROG

ANALOG PROGRAMMING INPUT - VOLTAGE (0-10V)

(3)

3.3

19

-S

NEGATIVE ERROR SENSE INPUT

2.7.5

20

X

NO CONNECTION

21

FFS-2

FAN STATUS - NORMALLY OPEN CONTACT

3.14

22

FFS-C

FAN STATUS - COMMON CONTACT

3.14

23

ACS-1

SOURCE POWER STATUS - NORMALLY OPEN CONTACT

3.14

24

X

NO CONNECTION

(1)

25

AUXRTN

AUXILIARY SUPPLY RETURN

(2)

3.11

26

5VAUX

AUXILIARY SUPPLY OUTPUT

3.11

27

X

NO CONNECTION

(1)

28

X

NO CONNECTION

29

OTS-2

OVERTEMP STATUS - NORMALLY OPEN CONTACT

3.14

30

OTS-1

OVERTEMP STATUS - NORMALLY CLOSED CONTACT

3.14

31

PSS-1

OUTPUT STATUS - NORMALLY OPEN CONTACT

3.14

32

IMON

ANALOG OUTPUT CURRENT MONITOR (0-5.5V)

(3)

3.13

33

ISET

CURRENT LIMIT SETPOINT MONITOR (0-10V)

(3)

3.7

34

X

NO CONNECTION

35

VRP2

RESISTIVE PROGRAMMING INPUT - VOLTAGE (0-10K)

3.3

36

VSET

OUTPUT VOLTAGE SETPOINT MONITOR (0-10V)

(3)

3.7

37

+S

POSITIVE ERROR SENSE INPUT

2.7.5

(1) These pins are left blank to provide voltage isolation between output
and a 5V aux supply which powers the remote inhibit control circuitry.
(2) These signals are referenced to auxrtn (pin 25).
(3) These signals are referenced to -s (pin 19).