Installation and Setup

Table 2-4

Default communication parameters for Series 1000/2000/3000 transmitters

Default values

Transmitter

Physical layer

Protocol

Baud

Data
bits

(1)

(1) ProLink II automatically sets data bits appropriately for the configured protocol. Even though a data bits parameter may be

configured in the transmitter, you do not need to configure it in ProLink II. HART protocol is always 8 data bits. If your transmitter
is configured for Modbus with 7 data bits, specify Modbus ASCII; if your transmitter is configured for Modbus with 8 data bits, specify
Modbus RTU.

Stop
bits

Parity

Address

Model 1500/2500

Bell 202

(2)(3)

(2) Connection to primary mA output, or to HART clips (Model 2400S and Model 2200S transmitters only).
(3) Except Model 1500 transmitter with the Filling and Dosing application. The Model 1500 transmitter with the Filling and Dosing

application does not support Bell 202 / HART communication.

HART

(4)

(4) HART/Bell 202 parameters are not configurable. The settings shown here are always in effect.

1200

8

1

odd

0

RS-485

(5)

(5) Connection to RS-485 terminals.

Modbus RTU

9600

8

1

odd

1

Model 1700/2700
Analog

Bell 202

(2)

HART

(4)

1200

8

1

odd

0

RS-485

(5)(6)

(6) Available only on Model 1700/2700 transmitters with analog outputs.

HART

1200

8

1

odd

0

Model 1700/2700 I.S.,
Model 2700 Config. I/O

Bell 202

(2)

HART

(4)

1200

8

1

odd

0

Model 2200S

Bell 202

(2)

HART

(4)

1200

8

1

odd

0

Model 2400S Analog

Bell 202

(2)

HART

(4)

1200

8

1

odd

0

RS-485

Modbus
(RTU or ASCII)

Auto-
detect

Auto-
detect

Auto-
detect

Auto-
detect

1

Series 3000

Bell 202

(2)

HART

(4)

1200

8

1

odd

0

RS-485

(5)

Modbus RTU

9600

8

1

odd

1

Table 2-5

Default communication parameters for LF-Series transmitters

Default values

Transmitter

Physical layer

Protocol

Baud

Data
bits

(1)

(1) ProLink II automatically sets data bits appropriately for the configured protocol. Even though a data bits parameter may be

configured in the transmitter, you do not need to configure it in ProLink II. HART protocol is always 8 data bits. If your transmitter
is configured for Modbus with 7 data bits, specify Modbus ASCII; if your transmitter is configured for Modbus with 8 data bits, specify
Modbus RTU.

Stop
bits

Parity

Address

DIN rail

Bell 202

(2)(3)

(2) Connection to primary mA output.
(3) Except transmitters with the Filling and Dosing application. Transmitters with the Filling and Dosing application do not support

Bell 202 / HART communication.

HART

(4)

(4) HART/Bell 202 parameters are not configurable. The settings shown here are always in effect.

1200

8

1

odd

0

RS-485

(5)

(5) Connection to RS-485 terminals.

Modbus RTU

9600

8

1

odd

1

Field-mount with output
option 1 or 3

Bell 202

(2)

HART

(4)

1200

8

1

odd

0

RS-485

(5)

HART

1200

8

1

odd

0

Field-mount with output
option 4

Bell 202

(2)

HART

(4)

1200

8

1

odd

0