2.5.1

Connection diagrams

Use the following diagrams to make the connection between your PC and the transmitter.

Figure 2-1

Typical HART/Bell 202 connection to transmitter or multidrop network

Model 7835 EXD

(2)

3

4

MVD

Direct Connect

with no barrier

(3)

3

4

MVD Direct Connect with
I.S. barrier

• To barrier

(4)

13

14

• To core processor

(3)

3

4

Core processor

3

4

(1) If connecting to terminals 1 and 2, terminals must be externally powered, with a minimum of 250

Ω

and 17.5 volts. Requirement does

not apply to service port.

(2) Transmitter version with advanced electronics option only.
(3) Connection is not intrinsically safe.
(4) Intrinsically safe connection.

Table 2-1

Transmitter terminals for ProLink II connections continued

Transmitter

Terminals for connection type

HART/Bell 202

HART/RS-485

Modbus/RS-485

Service port

PV+

PV–

A

B

A

B

A

B

VIA
TOR

VIA
TOR

or

DCS or

PLC

R1

R3

R2

Primary mA output terminals

Transmitter

USB plug

Bell 202 signal

converter

Notes:
• Connect the HART interface leads to the primary mA output of the transmitter, or to any point on the network.
• If necessary, use any combination of R1, R2, and R3 to bring the total resistance within 250–600

Ω.

(250–1000

Ω for RFT9712 and RFT9739).

• If no other device is connected to the primary mA output, add R1.
• If the primary mA is connected to a DCS or PLC with R2:

• Where R2 is insufficient, add R1 to bring R1+R2 into range.
• Where R2 is absent, add R3.