2.5.1
Connection diagrams
Use the following diagrams to make the connection between your PC and the transmitter.
Figure 2-1
Typical HART/Bell 202 connection to transmitter or multidrop network
Model 7835 EXD
3
4
MVD
™
Direct Connect
™
with no barrier
(3)
3
4
MVD Direct Connect with
I.S. barrier
• To barrier
(4)
13
14
• To core processor
3
4
Core processor
3
4
(1) If connecting to terminals 1 and 2, terminals must be externally powered, with a minimum of 250
Ω
and 17.5 volts. Requirement does
not apply to service port.
(2) Transmitter version with advanced electronics option only.
(3) Connection is not intrinsically safe.
(4) Intrinsically safe connection.
Table 2-1
Transmitter terminals for ProLink II connections continued
Transmitter
Terminals for connection type
HART/Bell 202
HART/RS-485
Modbus/RS-485
Service port
PV+
PV–
A
B
A
B
A
B
VIA
TOR
VIA
TOR
or
DCS or
PLC
R1
R3
R2
Primary mA output terminals
Transmitter
USB plug
Bell 202 signal
converter
Notes:
• Connect the HART interface leads to the primary mA output of the transmitter, or to any point on the network.
• If necessary, use any combination of R1, R2, and R3 to bring the total resistance within 250–600
Ω.
(250–1000
Ω for RFT9712 and RFT9739).
• If no other device is connected to the primary mA output, add R1.
• If the primary mA is connected to a DCS or PLC with R2:
• Where R2 is insufficient, add R1 to bring R1+R2 into range.
• Where R2 is absent, add R3.