SPECIFICATIONS

40

Table 6

Electrical specifications

Liebert NXL Model Size

250

300

400

Input Parameters

Input Voltage to Rectifier, VAC

480V 3-phase, 3-wire

Input Voltage to Bypass, VAC

480V 3-phase, 3- or 4-wire

Permissible Input Voltage Range, VAC

70% to 110%

Input Frequency, Hz

60

Permissible Input Frequency Range, Hz

55 to 65

Input THDi at nominal voltage at full load, %

<10% with 6-pulse and passive filter

Input Power Factor at nominal voltage

>= 0.92

Flexi Power Walk-In, sec

3 to 30 (selectable) in 1 sec. Increments

Battery & DC Parameters

Battery Type

VRLA (Valve Regulated Lead Acid) or FLA

(Flooded Lead Acid)

Nominal Battery Bus, VDC

480V

Battery Float Voltage, VDC

540V

End-Cell Voltage, VDC

384 (for VRLA / FLA)

DC Ripple Voltage in float & Const V Ch.mode, %

<1 (RMS value) < 3.4% Vpp

Temperature Compensated Battery Charging

Standard (with temperature probe)

Output Parameters

Inverter Type

IGBT-based Sine-Sine PWM Controlled

Output Power, kW

225

270

360

Output Voltage

480VAC, 3-ph, 4-w

Output Voltage Regulation, %

< 1% (3-phase RMS average)

Output Voltage Regulation (100% Unb. Load)

< 2% (3-phase RMS average)

Output Frequency, Hz

60

Output Frequency Regulation, %

± 0.1

Output THDu at Nominal Voltage (Linear Load), %

<2%

Output THDu at nominal voltage Including a 100kVA Non Linear

Load per EN 62040-3, %

2.5% (max)

Capacity to Handle Step Load, %

0-100 or 100-0

Transient Recovery

(Linear Loads), %

, msec

within 5% peak to peak in one-line cycle

Capacity to Handle Leading PF Load

Up to 0.8 with the following ratings:

a - 0.5 lag to 0.9 lag

a - Subject to maximum kVA rating

b - 0.9 lag to Nom

b - Subject to maximum kW rating

c - at 0.95 Lead

c - Subject to maximum. kW rating

d - at 0.9 Lead

d - Subject to 12,5% kW derate or same rating

and 10°C temp. derate

e - at 0.8 Lead

e - Subject to 25% kW derate or 12,5% kW derate and

10°C Temp. Derate

Voltage Displacement, ° el

120° ±1° el (with 100% unbalanced load)

Compliance to

FCC

Class-A

Standard

Overload Conditions, % FL

110% for 60 minutes
125% for 10 minutes

150% for 1 minute