Operation

22

2.3.4 Off Battery

The battery plant can be disconnected from the UPS, if required for battery maintenance, by opening

the module battery disconnect (MBD) circuit breaker. In this situation the UPS module will continue

to supply conditioned power to the critical load, but if input power fails the UPS system cannot supply

power to the load.

Figure 27 Load on UPS, battery not available

2.3.5 Emergency Module Off

The Local Emergency Module Off (LEMO) mode will transfer the critical load to the bypass line and

remove power from all UPS module components except the controls, bypass circuit breaker and the

static switch.
The Emergency Module Off control is a guarded pad next to the display touchscreen (Figure 2).
Lift the cover and press the pad. The load will be transferred to bypass, and the battery (MBD), input

and output circuit breakers will be opened (tripped). Refer to 2.5 - Shutdown Procedures.

Figure 28 Emergency modules off

!

CAUTION

When the UPS system is operating with the module battery disconnect (MBD) circuit

breaker(s) open, the critical load is not protected from loss of the utility source power.

Bypass

Input

Battery

System

DC Bus

Module

Output

BFB

CB2

CB1

MBD

Bypass

Battery

System

DC Bus

Module

Output

BFB

CB2

CB1

MBD

Input