Figure 22 battery cycle monitor—clear log, 8 metering, 9 help – Emerson 250-400kVA User Manual

Page 25: 10 reset, 11 silence, 3 modes of operation, 1 load on bypass, Figure 23 load on bypass (ups not available), Metering, Help

background image

Operation

19

Clear Log—This command resets the Date of First Discharge Cycle. A dialog box will warn that the

data will be permanently lost and should downloaded before proceeding (see Figure 22).

Figure 22 Battery cycle monitor—clear log

2.2.8 Metering

This button will place the metering tables in the multipurpose window.

2.2.9 Help

This button will display the help menu.

2.2.10 Reset

This button will reset any non-active latched events.

2.2.11 Silence

This button will silence the audible alarm.

2.3

Modes of Operation

This section illustrates the flow of power through circuit breakers, switches and UPS components

during various modes of operation. The same modes of operation apply to all configurations of the Lie-

bert NXL. Highlighted (thick) lines in the diagrams indicate power flow and power availability.
These illustrations do not show an alternate power source (generator) and automatic transfer switch

(external to the UPS) that might be present at your installation.

2.3.1 Load on Bypass

Load on Bypass, with the UPS not available, is shown in Figure 23. The UPS system could be in this

mode of operation during either initial startup or UPS system shutdown and isolation for mainte-

nance.

NOTICE

Risk of equipment damage. When the critical load is being supplied power from the bypass

line, it is exposed to utility failure and fluctuations.

Figure 23 Load on bypass (UPS not available)

Bypass

Input

Battery

System

DC Bus

Module

Output

BFB

CB2

CB1

MBD