beautypg.com

Matching battery cabinets—optional, Table 2 battery voltage, nominal and float, Table 3 battery retorque values – Emerson 250-400kVA User Manual

Page 42: Table 2, Battery voltage, nominal and float, Table 3, Battery retorque values, Warning

background image

Maintenance

36

Because individual battery characteristics are not identical and may change over time, the UPS mod-

ule is equipped with circuitry to equalize battery cell voltages. This circuit increases charging voltage

to maintain flooded type battery cells at full capacity.

Matching Battery Cabinets—Optional

Although the individual battery cells are sealed (valve-regulated) and require only minimal mainte-

nance, the Battery Cabinets should be given a periodic inspection and electrical check. Checks should

be performed at least annually to ensure years of trouble-free service.
Voltage Records: With the Battery Cabinet DC circuit breaker closed and the connected UPS oper-

ating, measure and record battery float voltage. With the DC circuit breaker open, measure and

record the nominal (open circuit) voltage. Both these measurements should be made across the final

positive and negative terminal lugs. Compare these values with those shown below. The recorded

nominal voltage should be no less than the value shown; while the recorded float voltage should be

within the range shown. If a discrepancy is found, contact Liebert Services.

Power Connections: Check for corrosion and connection integrity. Visually inspect wiring for dis-

colored or cracked insulation. Clean and/or retighten as required. Refer to torque specifications in

Table 4.
Battery Cell Terminals: Check for discoloration, corrosion and connection integrity. Clean and

tighten if necessary. Note that when installing a new battery, the initial torque value is 5 lb.-in. more

than the retorque value. Table 8 shows battery retorque values.

If you have a different model battery, contact Liebert Services for the required torque value.
To access battery cell terminals, disconnect the inter-tier cable and two shelf retaining screws. Once

disconnected, insulate (with protective boot or electrical tape) the cables to prevent accidental shorts.

The battery shelf can now be pulled out. Tighten each terminal connection to the retorque value.

When replacing a battery, the terminal connections must be cleaned and tightened. Disconnect and

insulate the cables connected to the battery. Secure each battery shelf with retaining screws when

maintenance is complete.

!

WARNING

Risk of electric shock, explosive reaction, hazardous chemicals and fire. Can cause equipment

damage, personal injury and death.
Do not use equalize charging with valve-regulated, lead-acid batteries. Refer to the battery

manufacturer’s manual, available on the manufacturer’s Web site, for specific information

about equalize charging.

Table 2

Battery voltage, nominal and float

Number of Cells

Battery Voltage, VDC

Nominal

Float

240

480

527 - 552

Table 3

Battery retorque values

Battery

Manufacturer

Battery Model

Number

Retorque

Value

C&D batteries

UPS12-300MR

110 in-lb

UPS12-350MR

110 in-lb

UPS12-400MR

110 in-lb

UPS12-490MR

110 in-lb

UPS12-540MR

110 in-lb

Enersys

HX205-FR

65 in-lb

HX300-FR

65 in-lb

HX330-FR

65 in-lb

HX400-FR

65 in-lb

HX500-FR

65 in-lb