beautypg.com

6 reporting a problem, 7 corrective actions, Reporting a problem – Emerson 250-400kVA User Manual

Page 44: Corrective actions

background image

Maintenance

38

3.6

Reporting a Problem

If a problem occurs within the UPS, review all alarm messages along with other pertinent data. Con-

tact Liebert Services at 1-800-LIEBERT to report a problem or to request assistance.

3.7

Corrective Actions

For each alarm message on the Display Screen, you can find the recommended corrective action in
Table 7.

3.8

Upstream Feeder Circuit Breaker Setting Inspections

During normal UPS operations, short-term overload current demand from the bypass source may

reach 10 times the UPS output current rating. This overload current demand may be caused by the

magnetizing inrush current of one or more downstream transformers (i.e., power distribution units)

or faults on downstream branch circuits. The instantaneous trip point(s) of the upstream bypass

feeder breaker(s) must be set to support these temporary overloads. The magnitude of short-term

overload bypass current demand is typically six to eight times the UPS current rating, but must be

determined by analysis on a per-site basis. This analysis, generally known as an End-to-End Fault

Coordination Study, must be done by a registered professional engineer experienced in this activity

and familiar with local codes and related requirements.
Liebert strongly recommends periodic inspections of the bypass feeder breaker instantaneous trip set-

tings, as well as the module input (rectifier) feeder breaker trip settings, to ensure that they are cor-

rect. For a variety of reasons, although typically during circuit breaker maintenance procedures by

others, trip settings have been known to be inadvertently left improperly set. Correct trip setting of

these circuit breakers is most important to achieving high-availability from your Liebert UPS system.

For further information regarding proper trip settings for your feeder breakers, call 1-800-LIEBERT.

NOTE
The instantaneous trip setting of the breaker feeding the UPS bypass input should be high

enough to accommodate short-duration overloads. The bypass static switch power path inside

the UPS can draw up to 10 times the system’s rated current for up to three cycles.

NOTE
While Liebert can provide typical guidelines, the responsibility for the proper breaker trip

settings outside the Liebert-manufactured UPS equipment resides with the owner. Contact

Liebert Services at 1-800-LIEBERT for further details.