beautypg.com

Figure 3 main display screen, typical, Figure 4 mimic display, Figure 3 – Emerson 250-400kVA User Manual

Page 12: Main display screen, typical, Figure 4, Mimic display

background image

Operation

6

Figure 3

Main Display Screen, typical

Figure 4

Mimic display

Bypass Input—Displays the bypass input voltage and the bypass input frequency. The bypass cir-

cuit breaker (BFB) is to the right of this block. The circuit breaker status is shown as open or closed.
UPS Input Power—Displays the UPS input voltage, current and frequency. The input circuit

breaker (CB1) is to the right of this block. The circuit breaker status is shown as open or closed.
Battery Block—Displays the battery voltage and the charge or discharge current to or from the bat-

tery. Pressing this icon switches among the connected battery strings. The Module Battery Discon-

nect (MBD) is to the right of this block. The circuit breaker status is shown as open or closed.
DC Bus—Displays the DC Bus voltage and the state of the battery charger.
Load—Displays the output line voltage, phase voltage, current, kVA, kW, power factor and fre-

quency. The critical load current per phase is also displayed in this block. During an overload, the

time remaining before transfer is displayed at the bottom of the load box. After an overload transfer,

retransfer timeout is displayed at the bottom of the load box.

Mimic

Display

Active

Event

Window

Multipurpose

Display

Menu

Bar

INPUT

A

B

C

L-L

0

0

0

V

I

0

0

0

A

Freq

0.0Hz

BATTERY 1 OF 4

Voltage Disable
Temp

Disable

T

BYPASS

A

B

C

L-L

0

0

0

V

Freq

0.0Hz

Voltage

0V

Current Float

CB1

BFB

MBD

BIS1

CB2

Legend
Inlet Air Temp 0°C

A

B

C

L-L

0

0

0

V

L-N

0

0

0

V

I

0

0

0

A

KVA

0

0

0

%

KW

0

0

0

%

PF

0.0

0.0 0.0

KVA/KW

0/

0

Freq

0.0Hz

Rexfer Timeout

00:00

MODULE OUTPUT

DC BUS

Bypass

Input

UPS

Input

Power

Battery

Block

Load