beautypg.com

Automatic transfers to bypass (overload condition), Figure 32 ) – Emerson 250-400kVA User Manual

Page 35

background image

Operation

29

Figure 32 Current-versus-time curves of overload capacity

2.6.2 Automatic Transfers to Bypass (Overload Condition)

The UPS system will initiate an automatic load transfer to the bypass line if an overload condition

exceeds the current-versus-time curve of overload capacity or if specified UPS system faults occur.

Load On Bypass is illustrated in Figure 24.
The Overload Transfer and Output Undervoltage alarm messages will initiate an automatic transfer

to bypass and the Load On Bypass message will be displayed. The active event window will display

the Automatic Transfer to Bypass message. Other UPS system faults will initiate an automatic trans-

fer to bypass followed immediately by the shutdown and isolation of the UPS system. Refer to 2.6.3 -

Automatic Transfers to Bypass, UPS System Faults.
In an automatic transfer to bypass the output and bypass circuit breakers do not overlap as they do in

a manual transfer. The static bypass switch is fired (closed), the output circuit breaker is opened, and

the bypass circuit breaker is closed. Bypass power is supplied to the critical load through the static

bypass switch during the short time while both circuit breakers are open.

NOTE
A load transfer to the bypass line will be completed whenever an automatic transfer to bypass

is initiated. If the OK to Transfer condition is present, the load transfer will be uninterrupted.

If the Static Switch Unable alarm message is present for any reason, the automatic transfer

will be interrupted for 40 to 120 milliseconds. Because of the reliability of the UPS components,

an interrupted load transfer is a very unlikely occurrence.

150%

125%

1 min

10 min

60min

110%