Operation

21

2.3.3 Input Power Failure—Load on Battery

If the utility AC power source fails or is outside the acceptable range, the battery plant becomes the

power source for the UPS module inverters. The UPS continues to supply power to the critical load

and also to the UPS controls.
Use the Battery Time screen at the UPS modules to monitor the present battery voltage compared to

the shutdown value. The time the battery can sustain the load depends on the size of the load and the

size and condition of the battery plant.
Alarm messages that indicate battery status are Battery Discharge, Low Battery and Battery Shut-

down. The voltage limits for these alarms are displayed on the UPS module Alarm Limit Settings

screen. These limits were selected for your installation by Liebert Services during initial startup. The

battery block in the UPS module Monitor/Mimic Display indicates Charge or Discharge and the cur-

rent in amperes.

Figure 26 Input power fail, load on battery

Bypass

Input

Battery

System

DC Bus

Module

Output

BFB

CB2

CB1

MBD