Figure 13 battery management parameters – Emerson 250-400kVA User Manual

Page 19

background image

Operation

13

Battery Test

• Auto Test—Enable/Disable (default: disabled)
• Test Cycle, weeks—1 to 26 (default: 13 weeks)
• Time of day, hh:mm—Set Hour and Minute; sets the start time of the automatic battery test
• Start Date, mm dd, yyyyy—Set Month, Day and Year
• Test Duration, minutes—Automatic, 0.5 minute to 30% of full load Operating Time

(default: automatic)

• Minimum Battery Voltage, lead-acid only—1.75VPC to 1.95VPC (default: 1.75VPC); this is the

minimum voltage the battery test will stop.

Low Battery Warning Time

• Low Battery Warning Time, minutes—2 to 60, depending on configured batteries (default: 5 min-

utes)

Battery Temperature

• Battery Temp Warning—30°C to 50°C (default: 40°C)
• Battery Temp Limit—35°C to 60°C (default: 50°C)
• Disconnect—Enable/Disable (default: disabled)

Figure 13 Battery Management Parameters

Cell Count Adjustment

• Cell Count Adjustment— -12 cells to +6 cells (default: 0)

Float Voltage

• Battery Float Voltage, Vpc—2.15 to 2.3 (default: 2.25)

NOTE
If Disconnect is set to “Enable’ and the Battery Temp Limit is met, the Battery breaker will

open.