Installation

17

Figure 11, DC Cable to Battery Terminals

CAUTION: The inverter is NOT reverse polarity protected
(negative and positive connected backwards). You must
verify the correct voltage polarity BEFORE connecting the
DC wires or damage may occur.

Crimped and sealed copper ring terminal lugs with a 5/16” hole should
be used to connect the DC wires to the inverter’s DC terminals.

Figure 12, DC Cable to Inverter’s DC Terminals

BATTERY

DC cable

with ring lug

bolt

flat washer

Nut

(½” wrench)

lock washer

battery

post

battery terminal

Temperature sensor

Verify that the DC cable lugs

are flush with the battery

terminals. Torque the battery

terminals from 10 to 12 ft-lbs.

DC cable

with ring lug

DC

terminal cover

(snaps on)

Inverter’s

DC terminal

5/16" (Kep nut with star-washer)

or Flange nut