Module status indicators, Led diagnostics, Troubleshooting d-13 – Yaskawa Profibus-DP Option Card CM061 User Manual
Page 65

Troubleshooting D-13
#
Module Status Indicators
The following LEDs indicates the status of the PROFIBUS-DP Option.
Table D.7 – Diagnostic LEDs
LED
Color
Indication/Function
PWR
Green
Lit when the +5V power to the electronics is OK.
Turned off if the +5V is below +4.5V (min)
Indicates the module status
OFF
Communication Option CPU not running.
Solid Green:
Initialization.
Flashing green:
Normal operation.
Solid Red:
Internal Communication Option error.
Flashing red:
error detected.
WD Red/Green
Other indication
Unspecified, Communication Option error
#
LED Diagnostics
The following table presents the faults displayed by the LEDs on the PROFIBUS-DP Option, their causes, and corrections.
Table D.8 – LED Diagnostics
LED Display
PWR
COM
ERR
WD
Content
Cause
Corrective Action
Power is not being supplied
from the drive.
• Check the main circuit wiring on the drive.
• Cycle drive power.
OFF OFF
OFF OFF
Power
OFF
Power is not being supplied to
the option unit due to poor
option unit connection.
• Turn of the drive power.
• Check the option unit connection to the
drive.
• Cycle drive power.
Solid
Green
OFF
Solid
Red
Solid
Red
CPU
Error
Option unit CPU error.
• Cycle drive power.
• Replace option unit if fault persists.
Solid
Green
OFF
Solid
Red
Flashing
Red
Drive
Error
Error in Drive unit.
• Cycle drive power.
• Replace drive if fault persists.
Solid
Green
OFF
Flashing
Red
Solid
Green
Com
Error
A fault has occurred rendering
communication impossible.
• Check whether the address set in the
PROFIBUS-DP Master differs from the
address of the option unit.
• Check that the master is functioning
properly.
• Check that the termination resistor is
correctly connected to the communication
line.
• Check whether the communication line is
correctly connected (disconnected or poor
connection).
• Check that the communication line is
separated from the main power line.
Solid
Green
Solid
Green
Flashing
Red
Solid
Green
Com
Error
A fault has occurred rendering
communication impossible.
• Check whether the address is duplicated
with any other devices within the
PROFIBUS-DP network.
Solid
Green
Solid
Green
OFF
Solid
Green
CPU
Init
Option unit under initialization
• Wait until the WD LED is flashing
Solid
Green
Solid
Green
OFF
Flashing
Green
Normal
Normal communication
possible.