Module status indicators, Led diagnostics, Troubleshooting d-13 – Yaskawa Profibus-DP Option Card CM061 User Manual
Page 65

Troubleshooting D-13
#
Module Status Indicators
The following LEDs indicates the status of the PROFIBUS-DP Option.
Table D.7 – Diagnostic LEDs
LED
Color
Indication/Function
PWR
Green
Lit when the +5V power to the electronics is OK. 
Turned off if the +5V is below +4.5V (min) 
Indicates the module status
OFF
Communication Option CPU not running.
Solid Green:
Initialization.
Flashing green:
Normal operation.
Solid Red:
Internal Communication Option error.
Flashing red:
error detected.
WD Red/Green
Other indication
Unspecified, Communication Option error
#
LED Diagnostics
The following table presents the faults displayed by the LEDs on the PROFIBUS-DP Option, their causes, and corrections.
Table D.8 – LED Diagnostics
LED Display
PWR
COM
ERR
WD
Content
Cause
Corrective Action
Power is not being supplied 
from the drive. 
• Check the main circuit wiring on the drive. 
• Cycle drive power. 
OFF OFF
OFF OFF
Power 
OFF 
Power is not being supplied to 
the option unit due to poor 
option unit connection. 
• Turn of the drive power. 
• Check the option unit connection to the 
drive.
• Cycle drive power.
Solid 
Green 
OFF
Solid 
Red 
Solid 
Red 
CPU 
Error 
Option unit CPU error.
• Cycle drive power. 
• Replace option unit if fault persists. 
Solid 
Green 
OFF
Solid 
Red 
Flashing 
Red 
Drive 
Error 
Error in Drive unit.
• Cycle drive power. 
• Replace drive if fault persists. 
Solid 
Green 
OFF
Flashing 
Red 
Solid 
Green 
Com 
Error 
A fault has occurred rendering 
communication impossible. 
• Check whether the address set in the
PROFIBUS-DP Master differs from the 
address of the option unit. 
• Check that the master is functioning
properly.
• Check that the termination resistor is
correctly connected to the communication 
line. 
• Check whether the communication line is
correctly connected (disconnected or poor 
connection). 
• Check that the communication line is
separated from the main power line.
Solid 
Green 
Solid 
Green 
Flashing 
Red 
Solid 
Green 
Com 
Error 
A fault has occurred rendering 
communication impossible. 
• Check whether the address is duplicated
with any other devices within the 
PROFIBUS-DP network. 
Solid 
Green 
Solid 
Green 
OFF
Solid 
Green 
CPU 
Init 
Option unit under initialization
• Wait until the WD LED is flashing
Solid 
Green 
Solid 
Green 
OFF
Flashing 
Green 
Normal
Normal communication 
possible. 