Troubleshooting Check List

1:

The drive operates correctly without the PROFIBUS-DP Option installed

Drive model number ______________

2:

The PROFIBUS-DP Option is correctly and securely installed on the drive

PROFIBUS-DP Option Code number ______________

PROFIBUS-DP Option version ______________

3:

All network devices have unique addresses and drives are addressed between 1 and 99

Drive address____________

S1 _______

S2 _______

4:

The Run/Stop command source parameter, b1-02, is set correctly

b1-02 ____________

5:

The Frequency Reference command source parameter, b1-01, is set correctly

b1-01 ____________

6:

The correct cable type is used. Mfg.____________________ PN____________________

7:

All cable connections are correct per device schematic and are secure

8:

All cables have been checked for continuity. There are no breaks or shorts.

9:

Cable length between nodes is at least 1 meter

10:

Maximum segment and maximum network lengths do not exceed the maximum allowed

11:

The total stub lengths do not exceed the maximum allowed

12:

There are no more than 32 devices on each segment, including repeaters and controllers.

There are no more than 31 devices on each segment if no repeaters are used.

13:

The network is correctly terminated on each end and only at each end.

14:

The shield is continuous throughout the network and is properly grounded on each end.

15:

The network cable is routed away from any high voltage cable(s) or source(s).

16:

The correct GSD file is used. GSD file name ________________________________.GSD

17:

The controller scan list is configured to send and receive the correct amount of data.

18:

The PROFIBUS-DP LEDs are in their correct on/off states.

19:

All network devices have been tested for conformance with the PROFIBUS-DP specification.