beautypg.com

Fast i/o input data, Network communications 3-11 – Yaskawa Profibus-DP Option Card CM061 User Manual

Page 35

background image

Network Communications 3-11

#

Fast I/O Input Data

This area is used to transfer parameter data directly from the drive dual port RAM interface. The following tables detail the functions of the
fast I/O input data (Bytes 0 to 5)

Table 3.14 – 3 Word input/Output Message Fast I/O Input Data

Fast I/O Input Data (Drive -> PROFIBUS-DP Master )

Byte

Function

Bit

Note

0h @

RUN

1h

@ Zero Speed

2h @

Reverse

3h

@ Reset Signal

4h @

Frequency

Agree

5h

@ Drive Ready (Rdy)

6h

@ Minor Fault (Alarm)

0

7h

@ Major Fault

8h

@ OPE Error

9h

@ Fault Restart

Ah

Local/Remote

1 = Remote Operation

Bh

Multi-Function Output 1

1 = Close

Ch

Multi-Function Output 2

1 = Close

Dh

Multi-Function Output 3

1 = Close

Eh

Motor Select

1 = #2 Motor

1

Drive

Status

Fh

@ Zero Servo Complete

2

Frequency Reference MSB

3

Frequency
Reference

Frequency Reference LSB

0.1Hz
scaling is dependent on the setting of parameter o1-03

4

Output Current MSB

5

Output Current

Output Current LSB

Calculated value
Drive Current(Drive Rating/8192)