Drive Faults

The following is a table of faults that could be caused by the PROFIBUS-DP Option that will be displayed on the Operator Keypad, their
causes, and possible solutions. For any fault displayed on the operator that is not listed in the following table, please see the appropriate
drive technical manual.

Table 1.8 – Drive Faults

Fault

Content

Cause

Solution

BUS

Option PCB communications error

Communication is not established between
PROFIBUS-DP Master and the drive.

• Check PROFIBUS-DP communication LED display.

EF0

Option PCB external fault

Drive received an external fault command
from the Option PCB

• Check multi-function input settings
• Check PLC or controller program
• Eliminate cause of fault (machine device in fault state)

OPE05

Command selection fault

Parameter b1-01 is set to Option PCB and
no card is detected

• Install Option PCB

• Reprogram b1-01
• Replace the Option PCB

OPE06

Control mode selection fault

Parameter b1-02 is set to Option PCB and
no card is detected

• Install Option PCB
• Reprogram b1-02
• Replace the Option PCB

CPF20

Option PCB fault

Faulty J1/2CN connection

• Power cycle the drive
• Reseat the Option PCB
• Replace the Option PCB
• Replace the inverter

CPF21

Option PCB self-diagnostics fault

CPF22

Option PCB ID code fault

CPF23

Watch dog timer fault

Faulty Option PCB

• Replace the Option PCB