beautypg.com

Network cable is connected correctly, Run/stop operation parameter is set correctly, Frequency reference parameter is set correctly – Yaskawa Profibus-DP Option Card CM061 User Manual

Page 58: Troubleshooting d-6

background image

Troubleshooting D-6

#

Network Cable Is Connected Correctly

! Determine the type of connector on the PROFIBUS-DP Option. Connector Style A is an extended Phoenix connector. The

extension can be seen on the back of the connector as a small circuit board. Connector Style B is a standard phoenix connector
without any modifications.

! Connect the PROFIBUS-DP network cable to the PROFIBUS-DP Option. Refer to the appropriate connection drawing in Figure

C.2 below for your connector style.

! Use standard PROFIBUS-DP cable as specified by the PROFIBUS Organization.

C

o

n

n

e

c

to

r

S

ty

le

A

Reserved

Shield

1

B Out (RED)

4
5
6

Ground

A In (Green)

2

B In (RED)

A Out (Green)

3

C

o

n

n

e

c

to

r

S

ty

le

B

Reserved

Shield

1

2

A In/Out (Green)

3

B In/Out (RED)

4
5
6

Reserved

Reserved

Ground

Termination

S2

S1

Termination

S2

S1

Figure D.1 – PROFIBUS-DP Option Connections

#

Run/Stop Operation Parameter Is Set Correctly.

Parameter b1-02 needs to be set to the source of the drive’s Run/Stop command. If the receives the Run/Stop command from the
PROFIBUS-DP network, parameter b1-02 must be set to “3 – Option PCB”. Refer to the appropriate drive technical manual for further
explanation of this parameter.

Table D.1 - Run/Stop Reference Source

Parameter

Value

Description

0

Operator Keypad

1 External

Terminals

2 Serial

Communications

b1-02

3

Option PCB (PROFIBUS-DP Communications)

#

Frequency Reference Parameter Is Set Correctly

Parameter b1-01 needs to be set to the source of the drive’s frequency reference command. If the receives its frequency reference from the
PROFIBUS-DP network, parameter b1-01 must be set to “3 – Option PCB”. Refer to the appropriate drive technical manual for further
explanation of this parameter.

Table D.2 - Frequency Reference Source

Parameter

Value

Description

0 Operator

keypad

1 Terminals

2 Serial

Communications

3

Option PCB (PROFIBUS-DP Communications)

b1-01

4

Pulse input (Available on F7 and G7 drives only)