Installation 1-11

#

LED Diagnostics

The following table presents the faults displayed by the LEDs on the communication option, their causes, and solutions.

Table 1.7 – LED Diagnostics

LED Display

PWR

COM

ERR

WD

Content

Cause

Solutions

Power is not being supplied
from the drive.

• Check the main circuit wiring on the drive.

• Cycle drive power.

OFF OFF OFF OFF

Power

Off

Power is not being supplied to
the option unit due to poor
option unit connection.

• Turn of the drive power.

• Check the PROFIBUS-DP Option connection to the

2CN connector on the drive

• Cycle drive power.

Solid
Green

OFF

Solid
Red

Solid
Red

CPU Error

Option unit CPU error.

• Cycle drive power.
• Replace PROFIBUS-DP Option if fault persists.

Solid
Green

OFF

Solid
Red

Flashing
Red

Drive Error

Error in Drive unit.

• Cycle drive power.
• Replace PROFIBUS-DP Option if fault persists.

• Replace drive if fault persists.

Solid
Green

OFF

Flashing
Red

Solid
Green

Com Error

A fault has occurred rendering
communication impossible.

• Check whether the address set in the PROFIBUS-DP

Master differs from the address of the option unit.

• Check that the master is functioning properly.
• Check that the termination resistor is correctly

connected to the communication line.

• Check whether the communication line is correctly

connected (disconnected or poor connection).

• Check that the communication line is separated from

the main power line.

Solid
Green

Solid
Green

Flashing
Red

Solid
Green

Com Error

A fault has occurred rendering
communication impossible.

• Check whether the address is duplicated with any other

devices on the PROFIBUS-DP network.

Solid
Green

Solid
Green

OFF

Solid
Green

CPU Init

Option unit under initialization

• Wait until WD LED is flashing

Solid
Green

Solid
Green

OFF

Flashing
Green

Normal

Normal communication
possible.