Parameter access error messages, 16 word input/output message, 6 word input/output message – Yaskawa Profibus-DP Option Card CM061 User Manual
Page 36: Network communications 3-12

Network Communications 3-12
Parameter Access Error Messages
Whenever there is an invalid parameter access message, the drive will respond with an error message containing the fault code for that
particular error. Parameter access pertains only to16 Word and 6 word messages.
#
16 Word Input/Output Message
If an erroneous Parameter Access message is sent to the drive, the drive will respond with a fault message. The MSB of byte 16 of the fault
response will be set. If the fault is a read parameter data fault, byte 16 of the response message will contain 83h, read parameter function
code 03h with the MSB set. If the fault is a write parameter data fault, byte 16 of the response message will contain 90h, write parameter
function code 10h with the MSB set. Byte 19 will contain 2 and byte 21 will contain the specific error code. Refer to Table 3.15 below for
description of the possible error codes.
#
6 Word Input/Output Message
If an erroneous Parameter Access message is sent to the drive, the drive will respond with a fault message. The MSB of byte 4 of the fault
response will be set. If the fault is a read parameter data fault, byte 4 of the response message will contain 83h, read parameter function
code 03h with the MSB set. If the fault is a write parameter data fault, byte 4 of the response message will contain 90h, write parameter
function code 10h with the MSB set. Byte 7 will contain 2 and byte 9 will contain the specific error code. Refer to Table 3.15 below for
description of the possible error codes.
Table 3.15 – Parameter Access Fault Message Response
Error Code
Error Name
Details
01h
Function Error
Invalid function code
02h
Address Error
Parameter starting address greater than 600h
03h
Amount of Data Fault
Read or Write less than 2 words or more than 4 words
21h
Data Content Fault
Parameter exceeds upper and lower limits
22h Write
Fault
• Parameter change during running or under-voltage
• ENTER command was written during running
• Write attempted to read–only data or during under-voltage
• Write attempted during parameter data storage