Appendix A CONSTANTS LIST
E-55
H1-04
Multi-function Input (Terminal 6)
[Terminal 6 Sel]
0F
00 to FF
Possible
B
0F: Not used
H1-05
Multi-function Input (Terminal 7)
[Terminal 7 Sel]
0F
00 to FF
Possible
B
0F: Not used
H1-06
Multi-function Input (Terminal 8)
[Terminal 8 Sel]
08
00 to FF
Possible
B
08: External baseblock
H2-01
Multi-function Output
(Terminal 9-10)
[Terminal 9 Sel]
00
00 to FF
Possible
B
00: During running
H2-02
Multi-function Output
(Terminal 25)
[Terminal 25 Sel]
06
00 to FF
Possible
B
06: Converter ready
H2-03
Multi-function Output
(Terminal 26)
[Terminal 26 Sel]
0A
00 to FF
Possible
B
0A: Duirng MCON
H4-01
Multi-function Monitor AO
(terminal 21)
[Terminal 21 Sel]
07
0 to 50
Possible
B
07: Power at power supply side
H4-02
Gain (Terminal 21)
[Terminal 21 Gain]
1.00
-300.00 to
300.00
Possible
B
H4-03
Bias (Terminal 21)
[Terminal 21 Bias]
0
-32768 to
32767
Possible
B
H4-04
Multi-function Monitor AO
(Terminal 23)
[Terminal 23 Sel]
05
0 to 50
Possible
B
05: Current at power supply side
H4-05
Gain (Terminal 23)
[Terminal 23 Gain]
1.00
-300.00 to
300.00
Possible
B
H4-06
Bias (Terminal 23)
[Terminal 23 Bias]
0
-32768 to
32767
Possible
B
H4-07
Analog Output Signal Polarity
Selection
[AO Level Select]
1
0, 1
Possible
B
0: Without sign
1: With sign
L2-01
Momentary Power Loss
Detection
[PwrL Selection]
0
0 to 2
−
B
0: Fault
1: Operation continues within
power loss ridethrough time
2: Operation continues if control
power supply is hold.
Note: Even if L2-01 is set to 1 or
2, the VS-656DC5 may
detect a fault if momentary
power loss occurs during
regeneration.
L2-02
Momentary Power Loss
Ridethru Time
[PwrL Ridethru t]
1.0
0.0 to 2.0 s
−
B
L2-05
Undervoltage Detection Level
[PUV Det Level]
190
150 to 210 V
Possible
A
For 400 V class, doulbe the set-
ting.
L3-04
Operation Selection at Input OL
(OL1) Operation
[OL1 Time Delay]
1
0, 1
−
B
0: Continues operation.
1: Stops operation.
(cont’d)
Constant
No.
Name
[Display]
Initial
Value
Setting
Range
Change
during
Operation
Access
Level
Remarks