Yaskawa Varispeed-656 DC5 User Manual
Page 53

6 TROUBLESHOOTING
E-43
GF
Ground Fault
Ground Fault
The ground fault current at the VS-
656DC5 input side exceeded applox. 
50 % of the VS-656DC5 rated power.
• A ground fault can be caused
by motor burn damage, worn 
insulation, or a damaged cable.
• The wiring (r1, 1, t1) of the
voltage detection circuit at the 
power side differs from the 
wiring (R, S, T) of the main 
circuit.
• Check the wiring.
• Reset the fault after correcting 
its cause.
OC
Overcurrent
Overcurrent
The input current of the VS-656DC5 
exceeded the overcurrent detection 
level (200 % of rated current).
• A short-circuit occurred at the
output.
• Power supply drop
• The wiring (r1, 1, t1) of the 
voltage detection circuit at the 
power side differs from the 
wiring (R, S, T) of the main 
circuit.
• Improve the power supply.
• Check the wiring.
• Reset the fault after correcting 
its cause.
OV
DC Bus Overvolt
Overvoltage
The main circuit voltage exceeded the 
overvoltage detection level.
200 V class: Approx. 400 VDC 
or more
400 V class: Approx. 800 VDC 
or more
The regenerative energy from the 
motor is too large.
Adjust the regenerative load.
The power supply voltage is too 
high.
Decrease the voltage so it is 
within specifications.
The wiring (r1, 1, t1) of the 
power supply voltage detection 
circuit differs from the wiring (R, 
S, T) of the main circuit.
Decrease the voltage so it is 
within specifications.
OH(OH1)
Heatsnk Over temp
Cooling Fin Overheating
The temperature of the VS-656DC5 
cooling fins exceeded the setting in 
L8-02 or 105 
°C.
OH: The temperature exceeded the 
setting in L8-02 (Stopping method can 
be changed by L8-03.).
OH1: The temperature exceeded 105 
°C (Stopping method: Coast to stop).
The ambient temperature is too 
high.
Install a cooling unit.
There is a heat source nearby.
Remove the heat source.
The VS-656DC5 cooling fan has 
stopped.
Replace the cooling fan. (Contact 
your Yaskawa representative.)
Inrush Prevention Circuit Fault
(For 15 kW only)
A fault occurred in the inrush preven-
tion circuit.
The inrush current control relay is 
faulty and remains open.
• Turn OFF and then ON the
power supply.
• Replace the VS-656DC5 if the
fault continues to occur.
OL1
Conv Overloaded
VS-656DC5 Overload
The VS-656DC5 overload protection 
function has operated based on the 
internal electronic thermal valve.
• The load is too large.
• The VS-656DC5 capacity is 
too small.
• Check the size of the load.
• Replace the VS-656DC5 with 
one that has a larger capacity.
No display
Nothing appears on the Digital Opera-
tor.
The wiring is not correct.
Check the input wiring.
Incorrect Digital Operator con-
nection
• Connect the Digital Operator
again.
• Replace the Digital Operator.
The main circuit fuse (input AC 
fuse and DC fuse) and control 
power supply fuse are blown.
Replace the VS-656DC5 after 
correcting its cause.
Table 12 Fault Displays and Troubleshooting (cont’d)
Fault Display
Meaning
Probable Causes
Corrective Actions
