4 OPERATION
E-35
Switching Modes
Once the VS-656DC5 has been put into operation mode by pressing the Menu Key, the
Increment and Decrement Keys can be pressed to switch to other modes. Press the DATA/
ENTER Key to read/set the user constants in each mode.
Press the ESC Key to return to the mode display from the user constant display.
Press the DATA/ENTER Key twice to write a constant and then press the ESC Key to return
to the mode display. This is the most Basic operation, so you should remember it.
Fig. 14 Switching Modes
When running the VS-656DC5 after using Digital Operator, press the MENU Key to enter the opera-
tion mode and then press the DATA/ENTER Key from the operation mode display to bring up the
monitor display. Run commands cannot be received from any other display. (Monitor display in the
operation mode appears when the power is turned ON.)
Power ON (o1-02 = 1)
Select Language
English
MENU
ESC
DATA
ENTER
ESC
DATA
ENTER
ESC
DATA
ENTER
ESC
DATA
ENTER
A1-00 = 1
∗∗∗
English
Function b1
Sequence
ESC
DATA
ENTER
ESC
DATA
ENTER
x
Operation mode
x
Initialize mode
x
Programming mode
x
Modified constant mode
(Mode Display)
Monitor (Output voltage reference)
Operator display
language selection
Mode selection
Displays constants changed
from factory settings.
Function
(Constant Reading)
Constant Display
(Constant Setting)
DC5
∗ Main Menu ∗
Operation
Output V Command
U1-01 = 330V
None Modified
DC5
∗ Main Menu ∗
Initialize
DC5
∗ Main Menu ∗
Programming
DC5
∗ Main Menu ∗
Modified Consts
All modes/
constant status
Group b
Application
IMPORTANT