Appendix a constants list, A.1 monitor constant list – Yaskawa Varispeed-656 DC5 User Manual
Page 60

E-50
Appendix A CONSTANTS LIST
This section describes all the constants that can be monitored in the operation mode, and all the
constants that can be used in the initialize mode and programming mode.
The “Access Level” in the table shows in which access level the constant can be changed or
monitored. The meaning of each symbol for access level is as follows.
A.1
Monitor Constant List
The following table shows the constants that can be monitored in the operation mode.
Q
Can display the constant and change the setting by selecting QUICK-START.
B
Can display the constant and change the setting by selecting QUICK-START and BASIC.
A
Can display the constant and change the setting in all the access levels by selecting
QUICK-START, BASIC, and ADVANCED.
Constant No.
Name
[Display]
Unit
Access
Level
Remarks
U1-01
Output Voltage Reference
(before SFS)
[Output V Command]
1 V
Q
• Output signal level at multi-function analog output
200 V class: 10 V : 400 V
400 V class: 10 V : 800 V
(0 to +10 V output)
U1-02
Output Voltage Feedback
[Output V Feedback]
1 V
Q
• Output signal level at multi-function analog output
200 V class: 10 V : 400 V
400 V class: 10 V : 800 V
(0 to +10 V output)
U1-03
Output Current
[Output Current]
1 A
Q
• Output signal level at multi-function analog output
10 V: Rated current
(0 to +10 V output)
U1-04
Input Voltage
[Input Voltage]
1 V
Q
• Output signal level at multi-function analog output
200 Vclass: 10 V : 200 V
400 V class: 10 V : 400 V
(0 to +10 V output)
U1-05
Input Current
[Input Current]
1 A
Q
• Output signal level at multi-function analog output
10 V: Rated current
(0 to +10 V output)
U1-06
DC Side Power
[DC Side Power]
1 kW
Q
• Output signal level at multi-function analog output
10 V: Rated power
(0 to +10 V output)
U1-07
Power Supply Side Power
[AC Side Power]
1 kW
Q
• Output signal level at multi-function analog output
10 V: Rated power
(0 to +10 V output)
U1-08
Input Frequency
[Input Frequency]
0.01 Hz
Q
• Output signal level at multi-function analog output
10 V: 60 Hz
(0 to +10 V output)
U1-09
Primary Current
[Primary Current]
1 A
Q
• Output signal level at multi-function analog output
10 V: Rated current
(0 to +10 V output)