A.2 constant list other than monitor constants – Yaskawa Varispeed-656 DC5 User Manual
Page 64

E-54
A.2
Constant List Other Than Monitor Constants
Constant
No.
Name
[Display]
Initial
Value
Setting
Range
Change
during
Operation
Access
Level
Remarks
A1-00
Language selection for Digital
Operator display
[Select Language]
1
0, 1
−
Q
0: English
1: Japanese
A1-01
Constant access level
[Access Level]
2
0 to 9999
Possible
Q
0: Monitoring only
2: Quick-start (Q)
3: Basic (B)
4: Advanced (A)
A1-03
Initialize
[Init Parameters]
0000
0000 to 9999
−
Q
2220: Initializes using the User
Constants.
A1-04
Password 1 (Input)
[Enter Password]
0
0000 to 9999
−
Q
A1-05
Password 2 (Setting)
[Select Password]
0
0000 to 9999
−
−
B1-01
Voltage Reference Method
Selection
[Reference Source]
0
0
1 cannot be
set.
−
Q
0: Digital Operator
B1-02
Operation Method Selection
[Run Source]
1
0, 1
−
Q
0: Digital Operator
1: Control circuit terminals
B1-04
PRG Mode Run Command
Selection
[RUN CMD at PRG]
0
0, 1
−
A
0: Disabled
1: Enabled
B1-06
Read Sequence Input Twice
[Cntl Input Scans]
1
0, 1
−
A
0: Two scans every 3 msec
1: Two scans every 5 msec
C1-01
Acceleration Time
[Accel Time ]
10.0
0.0 to 6000.0
s
Possible
Q
C1-02
Deceleration Time
[Decel Time]
10.0
0.0 to 6000.0
s
Possible
Q
C5-01
AVR Proportional (P) Gain
[AVR P Gain]
20.00
1.00 to
300.00
Possible
B
C5-02
AVR Integral (I) Time
[AVR I Time]
0.500
0.000 to
10.000 sec
Possible
B
D1-01
Voltage Reference
[Voltage Command]
Refer to
Remarks.
300 to 340 V
(200 V class)
600 to 680 V
(400 V class)
Possible
Q
330 (200 V class), 660 (400 V
class)
F1-10
Excessive Frequency Deviation
Detection Level
[FDEV Detect Level]
3.0
1.0 to 10.0
Hz
−
A
F1-11
Excessive Frequency Deviation
Detection Delay Time
[FDEV Detect Time]
70.0
0.0 to 255.0
ms
−
A
H1-01
Multi-function Input (Terminal 3)
[Terminal 3 Sel]
24
00 to FF
Possible
B
24: Coasting to stop
H1-02
Multi-function Input (Terminal 4)
[Terminal 4 Sel]
14
00 to FF
Possible
B
14: Fault reset
H1-03
Multi-function Input (Terminal 5)
[Terminal 5 Sel]
0F
00 to FF
Possible
B
0F: Not used