3 p7 to p1000 feature specifications, P7 to p1000 feature specifications – Yaskawa P7 to P1000 User Manual
Page 7

3 P7 to P1000 Feature Specifications
YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide
7
3
P7 to P1000 Feature Specifications
Table 3 P7 to P1000 Feature Specifications
Feature
Item
P7
P1000
HP Range
200 V
240V 0.5 to 150 HP
240 V 0.75 to 175 HP
400 V
480V 0.5 to 500 HP
480 V 0.75 to 1000 HP
600 V
—
600 V 1.0 to 250 HP
Input Voltage
Rated Voltage
3-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 200-240 Vac
3-phase, 380-480 Vac
3-phase, 500-600 Vac
Motor types
—
Induction
Induction
PWM Carrier Frequency
Range
Refer to Appendix 1 P7 and P1000 Ratings
on page 18
Refer to Appendix 1 P7 and P1000 Ratings
on page 18
Maximum Output Frequency Hz
120 Hz
400 Hz
Keypad Design
Display
5 Line x 16 Character LCD
5 Line x 16 Character LCD
Copy Function
Yes
Yes
Digital Input Terminal
NPN/PNP
Switchable NPN/PNP
Switchable NPN/PNP
Digital output Terminal
Open Collector
0
0
Relay Output
2 x Form A, 1 x Form C
2 x Form A, 2 x Form C
Analog Output
Output Level
Two channels with independent level
selections
Channel 1:
0-10 V
Resolution: 10-bit plus sign
Channel 2:
0-10 V or –10 to +10 V
Resolution: 10 bit plus sign, or
4-20 mA
Resolution: 10-bit
Three channels with independent level
selections
Channels 1, 2 and 3:
0-10 V, or –10-+10 V
Resolution: 11 bit plus sign or
or 4-20 mA
Resolution: 10-bit plus sign
Pulse Input
Qty:
—
1
Input Frequency
—
1-32 kHz
Quick Disconnect Terminals
Type
Yes
Yes
Auto Tuning
Methods
Primary Resistance
Rotating, Stationary, Primary Resistance,
Rotational V/f
Preset Speeds
Qty.
5
17
Speed Search
Bi/Uni-Directional
Bi-Directional
Bi-Directional
Method
Current/Speed
Current/Speed Estimation
Auto Restart
Time Between
Attempts
0.5 to 600.0 sec (selectable)
0.5 to 600.0 sec (selectable)
Energy Savings Mode
Man/Auto
Man/Auto
Man/Auto
DC Injection Function
At Start/At Stop
At Start/At Stop +HSB during stop
At Start/At Stop +HSB during stop
Braking Function
DB Transistor
Built-in to 25 HP (200 V Class),
30 HP (400 V Class)
Built-in to 50 HP
Special
High Slip Braking
High Slip/Over-excitation Braking
Cooling Fan On/Off Control
Power/Run
Run Based
Selectable Always Active/During Run
Timer Function
On/Off Delay
On/Off Delay (0 to 3000 s)
On/Off Delay (0 to 3000 s)
Fault Code Additions
—
10 additional
10 with elapsed time stamp
Torque Limit/Current Limit/
Stall Prevention
—
Stall Prevention
During Accel/Run/Decel (V/f)
Software Current Limit (120%)
Stall Prevention
During Accel/Run/Decel (V/f)
Software Current Limit (120%)