13 Appendix 2 Parameter Cross Reference

YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide

41

Motor
Protection
Function

Motor Overheat
Fault Operation
Selection

L1-04

1

L1-04

1

L1-04

L1-04

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

Motor
Temperature
Input Filter Time

L1-05

0.20 s

L1-05

0.20 s

Momentary
Power Loss
Process

Momentary
Power Loss
Detection/
Operation
Selection

L2-01

2

L2-01

2

L2-01

L2-01

0: Disabled

0: Disabled

1: Power Loss Ride Thru Time

1: Recover within the
time set in L2-02

2: CPU Power Active

2: Recover as long as
CPU Power Active

3: KEB deceleration for
time set in L2-02

4: KEB deceleration as long as
CPU has power.

5: KEB deceleration to stop.

Momentary
Power Loss
Ride-Thru Time

L2-02

*

L2-02

**

*Dependent on duty rating parameter C6-01 and drive capacity
parameter o2-04.
**Dependent on drive capacity parameter o2-04

Momentary
Power Loss
Minimum
Baseblock Time

L2-03

*

L2-03

**

*Dependent on duty rating parameter C6-01 and drive capacity
parameter o2-04.
**Dependent on drive capacity parameter o2-04

Momentary
Power Loss
Voltage
Recovery Ramp
Time

L2-04

*

L2-04

**

*Dependent on duty rating parameter C6-01 and drive capacity
parameter o2-04.
**Dependent on drive capacity parameter o2-04

Undervoltage
Detection Level

L2-05

190 V

L2-05

190 V

380 V for a 400 class drive.
If E1-01 is set lower than 400, set 350 V for P1000.

Stall
Prevention
Function

Stall Prevention
Selection during
Acceleration

L3-01

1

L3-01

1

L3-01

L3-01

0: Disabled

0: Disabled

1: General purpose

1: General purpose

2: Intelligent

2: Intelligent

Stall Prevention
Level during
Acceleration

L3-02

120%*

L3-02

120% **

*Varies by duty rating parameter C6-01
**Upper limit is determined by L8-38.

Stall Prevention
Selection during
Deceleration

L3-04

1

L3-04

1

L3-04

L3-04

0: Disabled

0: Disabled

1: General purpose

1: General purpose

2: Intelligent

2: Intelligent

3: Stall Prevention with
braking resistor

4: Overexcitation Deceleration

5: Overexcitation Deceleration 2

Stall Prevention
Selection during
Run

L3-05

1

L3-05

1

L3-05

L3-05

0: Disabled

0: Disabled

1: Enabled
(Decel Time 1)

1: Enabled (Decel Time 1)

2: Enabled
(Decel Time 2)

2: Enabled (Decel Time 2)

Parameter Name

P7

P1000

Setting

Parameter

Default

Parameter

Default

P7

P1000