13 Appendix 2 Parameter Cross Reference
42
YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide
Stall
Prevention
Function
Stall Prevention
Level during
Run
L3-06
120%*
L3-06
120% **
*Varies by duty rating (Defaults: HD = 150%, ND = 120%)
**Upper limit is determined by parameters L8-38, Carrier
Frequency Reduction Selection.
Frequency
Detection
Speed
Agreement
Detection Level
L4-01
0.0 Hz
L4-01
0.0 Hz
—
Speed
Agreement
Detection Width
L4-02
2.0 Hz
L4-02
2.0 Hz
—
Frequency
Reference Loss
Detection
Selection
L4-05
1
L4-05
0
L4-05
L4-05
0: Stop
0: Stop
1: Run at L4-06 PrevRef
1: Run at the level set to L4-06
In P1000, the setting range for the frequency reference
when the reference is lost
(L4-06) is 0 to 100% (default: 80%)
Reference
Detection
Frequency
Reference Level
at Loss
Frequency
L4-06
80.0%
L4-06
80.0%
—
Fault Restart
Number of Auto
Restart Attempts
L5-01
0 times
L5-01
0 times
—
Auto Restart
Operation
Selection
L5-02
0
L5-02
0
L5-02
L5-02
0: No Fault Relay
0: Fault output not active
1: Fault Relay Active
1: Fault output active during
restart attempt
Maximum
Restart Time
After
Fault
L5-03
180.0 s
L5-04
10.0 s*
L5-03
L5-04
L5-05
180.0 s
180.0 s
1: Use time in
L5-04
L5-05
0*
* Use the above settings to have
the same fault reset method as the
P7 drive.
Overtorque
Detection
Torque
Detection
Selection 1
L6-01
0
L6-01
0
L6-01, L6-04
L6-01, L6-04
0: Disabled
0: Disabled
1: oL3 detection only active
during speed agree, operation
continues after detection
1: oL3 detection only active
during speed agree, operation
continues after detection
2: oL3 detection always active
during run, operation continues
after detection
2: oL3 detection always active
during run, operation continues
after detection
3: oL3 detection only active
during speed agree, output
shuts down on an oL3 fault
3: oL3 detection only active
during speed agree, output shuts
down on an oL3 fault
4: oL3 detection always active
during run, output shuts down
on an oL3 fault
4: oL3 detection always active
during run, output shuts down on
an oL3 fault
5: UL3 detection only active
during speed agree, operation
continues after detection
5: UL3 detection only active
during speed agree, operation
continues after detection
Parameter Name
P7
P1000
Setting
Parameter
Default
Parameter
Default
P7