Yaskawa P7 to P1000 User Manual
Page 30

13 Appendix 2 Parameter Cross Reference
30
YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide
S-Curve
Characteristics
S-Curve
Characteristic at
Accel Start
C2-01
0.20 s
C2-01
0.20 s
—
S-Curve
Characteristic at
Accel End
C2-02
0.20 s
C2-02
0.20 s
—
Torque
Compensation
Torque
Compensation
Gain
C4-01
1.00
C4-01
1.00
—
Torque
Compensation
Primary Delay
Time
C4-02
200 ms
C4-02
200 ms* *Determined by parameter o2-04, Drive Model Selection.
Carrier
Frequency
Drive Duty
Selection
C6-01
0
—
—
Parameter contents differ between P7 and P1000
C6-01
N/A
0: Heavy Duty
—
1: Normal Duty 1
—
2: Normal Duty 2
—
Carrier
Frequency
Selection
C6-02
Varies
by kVA
C6-02
7
C6-02
C6-02
0: Low Noise PWM
—
1: 2.0 kHz
1: 2.0 kHz
2: 5.0 kHz
2: 5.0 kHz
3: 8.0 kHz
3: 8.0 kHz
4: 10.0 kHz
4: 10.0 kHz
5: 12.5 kHz
5: 12.5 kHz
6: 15.0 kHz
6: 15.0 kHz
—
7 to A: Swing PWM 1-4
F: User-set
F: User-set
Carrier
Frequency
Upper Limit
C6-03
Varies
by kVA
C6-03
*
*Determined by parameter C6-02, Carrier Frequency Selection.
Carrier
Frequency
Lower Limit
C6-04
Varies
by kVA
C6-04
*
*Determined by parameter C6-02, Carrier Frequency Selection.
Carrier
Frequency
Proportional
Gain
C6-05
0
C6-05
*
*Determined by parameter C6-02, Carrier Frequency Selection.
Frequency
Reference
Frequency
Reference 1
d1-01
0.00 Hz
d1-01
0.00 Hz
—
Frequency
Reference 2
d1-02
0.00 Hz
d1-02
0.00 Hz
—
Frequency
Reference 3
d1-03
0.00 Hz
d1-03
0.00 Hz
—
Frequency
Reference 4
d1-04
0.00 Hz
d1-04
0.00 Hz
—
Jog Frequency
Reference
d1-17
6.00 Hz
d1-17
6.00 Hz
—
Parameter Name
P7
P1000
Setting
Parameter
Default
Parameter
Default
P7
P1000