Yaskawa P7 to P1000 User Manual
Page 43

13 Appendix 2 Parameter Cross Reference
YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide
43
Overtorque
Detection
Torque
Detection
Selection 1
L6-01
0
L6-01
0
6: UL3 detection always active
during run, operation continues
after detection
6: UL3 detection always active
during run, operation continues
after detection
7: UL3 detection only active
during speed agree, output
shuts down on an oL3 fault
7: UL3 detection only active
during speed agree, output shuts
down on an oL3 fault
8: UL3 detection always active
during run, output shuts down
on an oL3 fault
8: UL3 detection always active
during run, output shuts down on
an oL3 fault
—
9: UL6 detection only active
during speed agree, operation
continues after detection
—
10: UL6 detection always active
during run, operation continues
after detection
—
11: UL6 detection only active
during speed agree, output shuts
down on an oL3 fault
—
12: UL6 detection always active
during run, output shuts down on
an oL3 fault
Torque
Detection Level
1
L6-02
15%
L6-02
15%
—
Torque
Detection Time 1
L6-03
10.0 s
L6-03
10.0 s
—
Hardware
Protection
Internal
Dynamic
Braking Resistor
Protection
Selection (ERF)
L8-01
0
L8-01
0
L8-01
L8-01
0: Not Provided
0: Disabled
1: Provided
1: Enabled
Overheat
Pre-Alarm Level
L8-02
95 °C
L8-02
*
*Determined by drive capacity parameter o2-04.
Overheat Pre-
Alarm Operation
Selection
L8-03
3
L8-03
3
L8-03
L8-03
0: Ramp to stop
0: Ramp to stop
1: Coast to stop
1: Coast to stop
2: Fast Stop
2: Fast Stop
3: Alarm Only
3: Continue operation
(Alarm triggered)
—
4: Continue operation at reduced
speed as set in L8-19
Input Phase Loss
Detection Level
L8-06
KVA
Dep.
N/A
—
—
Output Ground
Fault Detection
Selection
L8-09
1
L8-09
1*
L8-09
L8-09
0: Disabled
0: Disabled
1: Enabled
1: Enabled
*Determined by drive capacity parameter o2-04.
Heatsink
Cooling Fan
Operation
Selection
L8-10
0
L8-10
0
L8-10
L8-10
0: During run only
0: During run only
1: Fan always on
1: Fan always on
Parameter Name
P7
P1000
Setting
Parameter
Default
Parameter
Default
P7
P1000