13 Appendix 2 Parameter Cross Reference
YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide
31
Frequency
Limits
Frequency
Reference Upper
Limit Value
d2-01
100.0%
d2-01
100.0%
—
Frequency
Reference Lower
Limit Value
d2-02
0.0%
d2-02
0.0%
—
Main Speed
Reference Lower
Limit Value
d2-03
0.0%
d2-03
0.0%
—
Jump
Frequency
Jump Frequency
1
d3-01
0.0 Hz
d3-01
0.0 Hz
—
Jump Frequency
2
d3-02
0.0 Hz
d3-02
0.0 Hz
—
Jump Frequency
3
d3-03
0.0 Hz
d3-03
0.0 Hz
—
Jump Frequency
Width
d3-04
1.0 Hz
d3-04
1.0 Hz
—
Frequency
Reference
Hold
Frequency
Reference Hold
Function
Selection
d4-01
0
—
—
d4-01
—
0: Disabled
—
1: Enabled
—
Trim Control
Level
d4-02
10%
d7-01
0.0%
H1-01 to
H1-06
d4-02
H1-01
to
H1-08
d7-01
d7-02
H1-01
to
H1-06
d7-02
0.0%
1C:+Speed
Ref
Setting value
44
Setting
value
No need
to set
1C:
+Speed
Ref
1D: -Speed
Ref
Setting value
45
No need
to set
-
(Setting
Value)
1D:
-Speed
Ref
V/f
Characteristics
Input Voltage
Setting
E1-01
240 V*
E1-01
230 V* *Double values for 400 V class drives.
V/f Pattern
Selection
E1-03
F
E1-03
F
E1-03
E1-03
0: 50 Hz
0: 50 Hz (constant torque 1)
1: 60 Hz saturation
1: 60 Hz (constant torque 2)
2: 50 Hz saturation
2: 60 Hz (constant torque 3),
50 Hz base
3: 72 Hz, 60 Hz base
3: 72 Hz (constant torque 4),
60 Hz base
4: 50 Hz VT1
4: 50 Hz VT1
5: 50 Hz VT2
5: 50 Hz VT2
6: 60 Hz VT1
6: 60 Hz VT3
7: 60 Hz VT2
7: 60 Hz VT4
8: 50 Hz HST1
8: 50 Hz HST1
9: 50 Hz HST2
9: 50 Hz HST2
A: 60 Hz HST1
A: 60 Hz HST3
B: 60 Hz HST2
B: 60 Hz HST4
C: 90 Hz (60 Hz base)
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f pattern
F: Custom V/f pattern
FF: Custom w/o limit
—
Parameter Name
P7
P1000
Setting
Parameter
Default
Parameter
Default
P7