13 Appendix 2 Parameter Cross Reference
44
YASKAWA PL.P1000.01 P7 to P1000 - Product Transition Guide
Hardware
Protection
Heatsink
Cooling Fan
Operation Delay
Time
L8-11
60 s
L8-11
60 s
—
Ambient
Temperature
Setting
L8-12
45 °C
L8-12
40 °C
Set the ambient temperature where the drive is being used.
oL2
Characteristics
Selection at Low
Speeds
L8-15
1
L8-15
1
L8-15
L8-15
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Soft CLA
Selection
L8-18
1
L8-18
1
L8-18
L8-18
0: Disabled
0: Disabled
1: Enabled
1: Enabled
oH Frequency
Reference
Reduction Level
L8-19
20.0%
N/A
—
—
oH1 Detection
Selection for Fan
Failure
L8-32
1
L8-32
1
L8-32
L8-32
0: Disabled
(Fan Alarm is Displayed)
0: Fault, Ramp to Stop
1: Enabled (oH1 Fault occurs) 1: Fault, Coast to Stop
—
2: Fast-Stop
—
3: Alarm Only
—
4: Alarm, Run at L8-19 Rate
Hunting
Prevention
Function
Hunting
Prevention
Function
Selection
n1-01
1
n1-01
1
n1-01
n1-01
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Hunting
Prevention Gain
Setting
n1-02
1.00
n1-02
1.00
—
High slip
Braking
High-Slip
Braking
Deceleration
Frequency Width
n3-01
5%
n3-01
5%
—
High-Slip
Braking Current
Limit
n3-02
150%
n3-02
120%*
*Upper limit is determined by parameters L8-38, Carrier
Frequency Reduction Selection.
High-Slip
Braking Dwell
Time at Stop
n3-03
1.0 s
n3-03
1.0 s
—
High-Slip
Braking
Overload Time
n3-04
40 s
n3-04
40 s
—
Display
Setting/
Selection
Drive Mode Unit
Monitor
Selection
o1-01
6*
o1-01
106*
*Refer to parameter H4-01 for details.
User Monitor
Selection After
Power Up
o1-02
1
o1-02
1
o1-02
o1-02
1: Frequency reference
1: Frequency reference
2: Output frequency
3: Output frequency
3: Output current
4: Output current
4: User-selected Monitor
(set by o1-01)
5: User-selected Monitor
(set by o1-01)
—
2: Direction
Parameter Name
P7
P1000
Setting
Parameter
Default
Parameter
Default
P7