SMA Solar Technology AG

Appendix D - Cable cross section and Torque

Installation Guide

SC125_560HE-IEN083220

87

12.2 AC connection

(1

Screw at NH fuse holder

(2

Copper bus bar perforated

(3

Bolt clamp

(4

Screw at fuse switch disconnector

(5

EriFlex bus bar perforated

Sunny Central

AC terminals

Max. cross

section

Torque

SC 100LV

5 x WFF 185

M12

(3

up to 240 mm²

14 - 31 Nm

SC 125LV

5 x WFF 185

M12

(3

up to 240 mm²

14 - 31 Nm

SC 150 Standard

5 x WFF 185

M12

(3

up to 240 mm²

14 - 31 Nm

SC 200 Standard

5 x WFF 185

M12

(3

up to 240 mm²

14 - 31 Nm

SC 200HE

Isolator

M12

(4

up to 240 mm²

32 Nm

SC 250 Standard

5 x WFF 185

M12

(3

up to 240 mm²

14 - 31 Nm

SC 250HE

Isolator

M12

(4

up to 240 mm²

32 Nm

SC 350 Standard

3 x Cu

Cu M12

(2

3 x 240 mm² per

phase

74 Nm

SC 350HE

3 x Cu

Cu M12

(2

3 x 240 mm² per

phase

74 Nm

SC 500HE

Isolator

M16

(5

up to 300 mm²

210 Nm

SC 560HE

Isolator

M16

(5

up to 300 mm²

210 Nm