5.1.10 EVR Cabling (optional)
With the Sunny Centrals 350 and 500, the EVR resistor has to be mounted on top of the Sunny
Central. Proceed as follows:
1. The EVR resistor between the rails has to be pushed onto the roof of the Sunny Central.
2. 9 screws at the protective bar of the EVR resistor have to be removed.
3. Protective bar has to be taken off to the front.
4. Connect the grounding cables in EVR resistor to the left side of the bolt (torque 21 Nm).
5. Fix the EVR resistor with both screws on the left and right side of the EVR resistor onto the rails.
6. Connect the power cables using the provided circuit diagram (torque 21 Nm).
7. Fix the protective bar with 9 screws onto the EVR resistor (torque 2.6 Nm).
☑ The EVR resistor is installed.
5.1.11 Sunny Central for installation near the sea (optional)
Optional package for Sunny Centrals in the case of installation near the sea. With this optional
package, the Sunny Centrals are protected against salt mist and comply to the requirements of
DIN EN 60721-3-3, class 3C2 "Environmental Conditions for Fixed Use,. Weather-protected". You
can find further information in the separate documentation.