beautypg.com

2 on-site inverter installation, 1 remove transport locks – SMA SC 100LV-560HE User Manual

Page 28

background image

Mounting the Device

SMA Solar Technology AG

28

SC125_560HE-IEN083220

Installation Guide

4.2 On-Site Inverter Installation

After both switch cabinets have been installed next to each other, the transport locks of the transformer
have to be removed, the seals have to be inserted and the individual cabinets have to be mechanically
and electrically connected for the final mounting in the electrical operating room. All necessary
materials required for the connection of the switch cabinets are included in the delivery.

4.2.1 Remove transport locks

The following table shows which type is delivered with transport locks.

The Sunny Centrals consist of two switch cabinet units, which are electrically and
mechanically connected on site. Make sure that both switch cabinets have the same serial
number. You will find the serial number on the type plate or on the transport packaging of
the Sunny Central switch cabinet.

Remove the transport locks.
In some Sunny Centrals, the transfomers and the sine filter are
secured with transport locks on the cabinet. The transport lock is a
metal angle which is fixed at the switch cabinet side.

Sunny Central

Transport lock Transformer Transport lock Sine filter

100LV

yes

no

125LV

yes

no

200

yes

no

200HE

no

no

250

yes

no

250HE

no

no

350

yes

no

350HE

no

no

500HE

no

yes

560HE

no

yes