420

Error text:

ADAPSCP overtemperature

Error type 3

Cause:

Heatsink temperature is too high (hardware threshold).

Corrective measures:

• Check function of the cooling fans of the inverter bridge.
• Clean soiled air inlet or heatsink.
• Ambient or cooling air temperature too high.
• If this error occurs frequently, contact the Sunny Central Serviceline.

421

Error text:

ADAPSCP Overvoltage DC voltage link

Error type 2

Cause:

DC voltage is too high on the solar generator side (hardware threshold).

Corrective measures:

• Immediately disconnect the solar generator from the Sunny Central! Risk of

damage to the Sunny Central!

• Check DC voltage.
• Check module wiring and system design.

No.