9.1.3 Warnings

No.

Description

281

Error text:

Ground fault or SPD defect

Error type 1

Cause:

The alert chain is interrupted (refer to the wiring diagram).

• Overvoltage protector damaged.
• Back-up fuse(s) damaged on the grid side or generator side (if present).
• The solar power system's insulation resistance is lower than the set threshold value.
• The transformer's biasing circuit breaker has tripped.

Corrective measures:

• Check fault signaling of the overvoltage protectors, and replace protector if

necessary.

• Check the back-up fuse(s) of the overvoltage protector and replace it / them if

necessary.

• Check the resistance of the solar power system.
• In the event of an insulation fault, check strings under load-free conditions. Separate

and connect individual strings to determine which string is faulty.

• Check the function of the ground fault monitor.
• Switch biasing circuit breaker of the transformer back on.

283

Error text:

cabinet Temp.

Error type 1

Cause:

The threshold value (parameter TMin or TMax) for the permissible cabinet temperature has
been breached (too high or too low).

Corrective measures:

• Check function of cabinet cooling fans.
• Clean or replace dirty air filters.
• Check ambient temperature, and adjust if necessary.