588

Error text:

Team contactor was opened

Error type 1

Cause:

The Team contactor was switched off by the Team current monitoring system.

Corrective measures:

• Check the triggering of the Team contactor.
• Check the Team current monitoring system (settings, defect).
• Check the Team current, may be too high due to asymmetrical current distribution.
• Contact the Sunny Central Serviceline.

No.