Failures and Warnings

User Manual

SC-BEN092751

51

9.1.4 Failures

No.

Description

104

Error text:

No Grid Synchronization

Error type 3

Cause:

Left-hand rotary field or internal device fault.

Corrective measures:

• Check (right-hand) rotary field.
• Check whether all internal fuses are switched on.
• Contact the Sunny Central Serviceline.

105

Error text:

Grid voltage too low

Error type 2

Cause:

Voltage on the AC side is below the permitted range.

Corrective measures:

• Check the grid connections.
• Check grid stability.

106

Error text:

Grid voltage too high

Error type 2

Cause:

Voltage on the AC side is above the permitted range.

Corrective measures:

• Check the grid connections.
• Check grid stability.

110

Error text:

UVW-Range

Error type 2

Cause:

Voltage on phase L1, L2, or L3 outside the permitted range.

Corrective measures:

• Check the grid connections.
• Check grid stability.