4 failures, Failures – SMA SUNNY CENTRAL User Manual
Page 51

SMA Solar Technology AG
Failures and Warnings
User Manual
SC-BEN092751
51
9.1.4 Failures
No.
Description
104
Error text:
No Grid Synchronization
Error type 3
Cause:
Left-hand rotary field or internal device fault.
Corrective measures:
• Check (right-hand) rotary field.
• Check whether all internal fuses are switched on.
• Contact the Sunny Central Serviceline.
105
Error text:
Grid voltage too low
Error type 2
Cause:
Voltage on the AC side is below the permitted range.
Corrective measures:
• Check the grid connections.
• Check grid stability.
106
Error text:
Grid voltage too high
Error type 2
Cause:
Voltage on the AC side is above the permitted range.
Corrective measures:
• Check the grid connections.
• Check grid stability.
110
Error text:
UVW-Range
Error type 2
Cause:
Voltage on phase L1, L2, or L3 outside the permitted range.
Corrective measures:
• Check the grid connections.
• Check grid stability.
- SUNNY PORTAL (75 pages)
- SB 2.5-1VL-40 (60 pages)
- SB 2.5-1VL-40 Service Manual (36 pages)
- SB 240 (78 pages)
- FLX Pro 17 (12 pages)
- FLX Series GSM Option Kit (48 pages)
- FLX Series Sensor Interface Option (51 pages)
- FLX Series PLA Option (62 pages)
- FLX Series (248 pages)
- 25000TL (52 pages)
- 25000TL Installation (40 pages)
- 25000TL Service Manual (46 pages)
- CBL-DC-CMB8-10 (24 pages)
- 25000TL Quick Installation Guide (36 pages)
- STP 60-10 Replacing a Defective Fan (12 pages)
- STP 60-10 Replacing Defective Surge Arresters (12 pages)
- Webconnect Systems in SUNNY PORTAL (69 pages)
- STP 12000TL (68 pages)
- STP 60-US-10 Installation (232 pages)
- 485 Data Module Type B (24 pages)
- STP 12000TL Quick Installation Guide (28 pages)
- 1000-US (52 pages)
- STP 24000TL-US (78 pages)
- STP 17000TL (60 pages)
- STP 20000TL (2 pages)
- SB 6000TL Service Manual (46 pages)
- MULTIFUNCTION RELAY (32 pages)
- SB 5000TL (60 pages)
- SB 5000TL Quick Installation Guide (32 pages)
- FANKIT01-10 (24 pages)
- SB 7700TL-US (28 pages)
- FANKIT02-10 (24 pages)
- SB 7700TL-US Installation (96 pages)
- SUNNY MINI CENTRAL (48 pages)
- DC Disconnect Switch For SB 3800-U (32 pages)
- SB 4000-US (100 pages)
- DB-DC-DISCON (4 pages)
- SB 3800-U (86 pages)
- POWER BALANCER (28 pages)
- SB 8000-US (104 pages)
- SB 11000TL‑US (40 pages)
- SMC 11000TL (24 pages)
- SBCBTL6 (36 pages)
- SB 11000TL‑US Installation (92 pages)
- SMC 11000TL Installation (96 pages)