2 default parameter settings, Default parameter settings – SMA SUNNY CENTRAL User Manual
Page 31

SMA Solar Technology AG
Parameters
User Manual
SC-BEN092751
31
6.2 Default Parameter Settings
The following table summarizes the main operating parameters, and includes the adjusting range and
default value of each parameter. The adjusting range and default value depend on the Sunny Central
model.
The parameters shown here with a gray background are only visible / adjustable after the installer
password has been entered (see section 5.4 "Entering the Password" (page 26)).
Tau-FP*
A damping function for the switching points helps minimize the number of
switchings and thus lengthen the service life of the Team contactor. This
parameter influences "Pac smoothed".
Parameter
Range
Default
VmppMin
275 - 400 V (Sunny Central LV)
450 - 600 V
300 V (Sunny Central LV)
450 V
dVreference
5 V - 200 V (Sunny Central LV)
5 V - 200 V
60 V (Sunny Central LV)
80 V
PsearchMpp
0 - 25000 W
device-specific setting
TsearchMpp
60 - 3600 s
600 s
dVtrack
1 - 10 V
5 V/TaMp
TcheckMpp
5 - 60 s
10 s
Mpp Factor
0.20 - 1.00
0.80
TrackCnt
5 - 20
7
VpvStart
300 - 600 V (Sunny Central LV)
450 - 800 V
400 V (Sunny Central LV)
600 V
Tstart
1 - 600 s
90 s
Twait
0 - 1800 s
600 s
PpvStop
0 - 10000 W
device-specific setting
Tstop
1 - 300 s
60 s
PacMax
3 - 500 kW
device-specific setting
TMax. cabinet
30 - 70 °C
50 °C
TMin. cabinet
-30 - 10 °C
-20 °C
Parameter
Description of the function