Failures and Warnings

User Manual

SC-BEN092751

53

206

Error text:

Emergency shutdown activated

Error type 4

Cause:

Own emergency shut-off of the inverter activated.

Corrective measures:

Deactivate the emergency shut-off and confirm the failure as described in section 9.2
"Confirming Errors at the Sunny Central Control" (page 58).

209

Error text:

DC Short circuit

Error type 4

Cause:

An internal short circuit was detected on the DC side within the inverter. The DC switch was
switched off.

Corrective measures:

• Check the Sunny Central from the outside.
• If possible, the Sunny Central should be externally isolated.
• Contact the Sunny Central Serviceline.

215

Error text:

heat sink fan fault

Error type 2

Cause:

• Motor overload switch for fan(s) for cooling the power module has tripped.
• Overtemperature protection for fan(s) for cooling the power module has tripped.
• Ambient or cooling air temperatures too high.

Corrective measures:

• Switch the motor overload switch back on.
• Check function of cooling fans.
• Clean soiled air inlet or heatsink.
• If this error occurs frequently, contact the Sunny Central Serviceline.