Failures and Warnings

SMA Solar Technology AG

52

SC-BEN092751

User Manual

111

Error text:

Grid frequency too high or too low

Error type 2

Cause:

Frequency on the AC side is outside the permitted range.

Corrective measures:

• Check the grid connections.
• Check grid stability.
• Check right-hand rotary field.

201

Error text:

Ground Fault 2 or plant temp. too high

Error type 2

Cause:

• The overtemperature fault chain is interrupted (refer to the wiring diagram).
• Cabinet overtemperature
• Transformer overtemperature
• Diode overtemperature
• The insultation resistance of the solar power system is lower than the set threshold

value.

• GFDI tripped.

Corrective measures:

• Check function of cooling fans.
• Clean or replace dirty air filters.
• Ambient or cooling air temperature too high.
• Check solar generator's insulation resistance.
• In the event of an insulation fault, separate and connect individual strings to detect the

faulty one.

• Check the function of the ground fault monitor.
• Check the GFDI (see "Additional Notes for Sunny Central M/P Inverters for Grounded

Operation of the Solar Generator").