Failures and Warnings

User Manual

SC-BEN092751

55

400

Error text:

internal failure of inverter bridge

Error type
2/3

Cause:

Internal inverter bridge failure (e.g. symmetry fault, board voltage, undertemperature,
sensor breakage).

Corrective measures:

If this error occurs frequently, contact the Sunny Central Serviceline.

402

Error text:
ser. com. with inverter bridge disturbed

Error type 2

Cause:

• The RS485 communication between the inverter bridge and the Sunny Central Control

is interrupted.

• The inverter bridge or the Sunny Central Control may be faulty.

Corrective measures:

• Check the RS485 wiring.
• If this error is always present, contact the Sunny Central Serviceline.

408

Error text:

PV Overvoltage

Error type 3

Cause:

DC voltage is too high on the generator side (software).

Corrective measures:

• Immediately disconnect the solar generator from the Sunny Central! Risk of

damage to the Sunny Central!

• Check DC voltage.
• Check module wiring and system design.