Messages

SMA Solar Technology AG

78

SB30TL_40TL_50TL-IA-IEN120231

Installation Guide

90

< Inst. code invalid >
The SMA Grid Guard Code entered
(personal installer password) is invalid.

• A valid SMA Grid Guard Code has

been entered.

< Grid param. locked >
The current country data set is locked.

• Enter the valid SMA Grid Guard

Code for changing the country data
set.

< Abort self-test >

• Contact the SMA Serviceline

(see section 15 ”Contact”
(page 101)).

< Changing grid param. not possible >

• The selected rotary switch setting for

the country configuration is not
programmed.

• The parameters to be changed are

protected.

< Ensure DC supply >

• DC voltage at the DC input is not

sufficient to run the main CPU.

• Check the setting of the rotary

switches (see section 5.4.2).

• Enter the SMA Grid Guard Code.

• Ensure sufficient DC voltage

(green LED lights up or flashes).

Event no. Display message and cause

Corrective measures