Opening and closing

SMA Solar Technology AG

64

SB30TL_40TL_50TL-IA-IEN120231

Installation Guide

7.3 Closing the Inverter

1. Check the DC plug connectors for correct polarity

and connect them to the inverter. To release the
DC connectors see section 7.2 ”Opening the
Inverter” (page 61).

2. To create the sealing on the inverter, all the DC

inputs have to be closed as follows:
– Insert the provided sealing plugs into the

unneeded DC plug connectors.
Do not insert the sealing plugs into the DC
inputs on the inverter.

– Insert the DC plug connectors with sealing plugs

into the corresponding DC inputs on the inverter.

DANGER!
Risk of lethal electric shock.

• Only connect the Electronic Solar Switch when the lid is closed.
• Only operate the inverter when the lid is closed so that the DC plug connectors

cannot be disconnected easily.