< High discharge curr. >
< Check generator >
The discharge current from the inverter and
the PV generator is too high.
This can be caused by a sudden grounding
fault, failure current or an actual fault in the
device.
The inverter interrupts grid feed
immediately after exceeding a limiting
value and then automatically re-connects
to the grid.
• Check the strings for ground faults, as
described in section 11.1 ”Checking
the PV Generator for a Ground
Fault” (page 79).
• The installer of the PV generator must
remedy the ground faults before you
re-connect the affected string.
37
< Resid.curr.too.high >
< Check generator >
• Check the strings for ground faults, as
described in section 11.1 ”Checking
the PV Generator for a Ground
Fault” (page 79).
• The installer of the PV generator must
remedy the ground faults before you
re-connect the affected string.
38
< DC overcurrent >
< Check generator >
An overcurrent condition occurs on the DC
side of the inverter and it switches off.
If this event occurs often:
• Check the layout and the wiring of
the PV generator.
39
< Waiting for DC start conditions >
< Start cond. not met >
The input power or the voltage of the PV
modules is not sufficient for feeding into the
grid.
• Wait for higher irradiation.
• If this event recurs at medium
irradiation, check the PV system
design and correct the connection of
the PV generator.
60 - 64
< Self diagnosis >
< Interference device >
• Contact the SMA Serviceline
(see section 15 ”Contact”
(page 101)).
65
< Self diagnosis >
< Overtemperature >
Inverter switches off due to excess
temperature.
• Ensure sufficient ventilation.
• Check heat dissipation, as described
in section 8.1 ”Checking Heat
Dissipation” (page 66).
66
< Self diagnosis >
< Overload >
• Contact the SMA Serviceline
(see section 15 ”Contact”
(page 101)).