Electrical Connection

SMA Solar Technology AG

30

SB30TL_40TL_50TL-IA-IEN120231

Installation Guide

7. Unscrew the AC cable gland's lock nut (G) and

remove the filler-plug from the cable gland.

8. Pull the cable through.
9. Raise the AC clamp terminals as far as they will go.

Seal in the AC cable gland
There is a two-part seal in the cable gland.
Remove the internal insert if necessary, e.g. to
lay a thicker cable.
The following guideline values apply:

• Cable cross-section with seal and insert: 12 mm … 16 mm
• Cable cross-section with seal only and without insert: 15 - 21 mm

NOTICE!
Risk of fire when connecting 2 conductors to a single terminal

If 2 conductors are connected to one terminal, a poor electrical contact can result in
overheating or a risk of fire.

• Never connect more than one conductor per terminal.