6  Commissioning

Installation Manual

SWWEBCONDM-IA-en-16

21

• Set the following parameters in Sunny Explorer (for setting parameters in a device,

see Sunny Explorer help):

• In the field Application-ID, enter the application ID of the grid operator gateway. You will

receive this value from your grid operator. You can enter a value between 0 and 16384.
The value 16384 indicates "deactivated".

• In the field Goose-Mac address, enter the MAC address of the grid operator gateway

from which the Speedwire/Webconnect data module is to receive the control commands.
You will receive this value from your grid operator.

☑ The receipt of grid operator control signals is now activated.

6.3 Managing a Small-Scale PV System with Sunny Explorer

6.3.1 Functions and Parameter Settings in Sunny Explorer

The following functions for system management are available in Sunny Explorer:

• Overview of the system status
• Graphic display of key PV system data, device data and energy values
• Parameterization of individual devices or entire device classes
• Simple diagnostics thanks to display of errors and events
• Data export of inverter energy values and events in CSV format
• Device updates

You can change the following parameters in Sunny Explorer:

• Device name of the inverter
• Automatic IP configuration On/Off
• DNS-IP, gateway IP, IP address, subnet mask
• Webconnect function On/Off

External communication > IEC 61850 configuration
Parameter

Value/range

Resolution

Default

Application-ID

0 to 16384

1

16384

Goose-Mac address

01:0C:CD:01:00:00

to

01:0C:CD:01:02:00

1

01:0C:CD:01:00:00