6 Commissioning
Installation Manual
SWWEBCONDM-IA-en-16
21
• Set the following parameters in Sunny Explorer (for setting parameters in a device,
see Sunny Explorer help):
• In the field Application-ID, enter the application ID of the grid operator gateway. You will
receive this value from your grid operator. You can enter a value between 0 and 16384.
The value 16384 indicates "deactivated".
• In the field Goose-Mac address, enter the MAC address of the grid operator gateway
from which the Speedwire/Webconnect data module is to receive the control commands.
You will receive this value from your grid operator.
☑ The receipt of grid operator control signals is now activated.
6.3 Managing a Small-Scale PV System with Sunny Explorer
6.3.1 Functions and Parameter Settings in Sunny Explorer
The following functions for system management are available in Sunny Explorer:
• Overview of the system status
• Graphic display of key PV system data, device data and energy values
• Parameterization of individual devices or entire device classes
• Simple diagnostics thanks to display of errors and events
• Data export of inverter energy values and events in CSV format
• Device updates
You can change the following parameters in Sunny Explorer:
• Device name of the inverter
• Automatic IP configuration On/Off
• DNS-IP, gateway IP, IP address, subnet mask
• Webconnect function On/Off
External communication > IEC 61850 configuration
Parameter
Value/range
Resolution
Default
Application-ID
0 to 16384
1
16384
Goose-Mac address
01:0C:CD:01:00:00
to
01:0C:CD:01:02:00
1
01:0C:CD:01:00:00