Illustration 5.13 Auxiliary Interfaces

5.9 RS-485 and Ethernet Connections

RS-485

Terminate the RS-485 communication bus at both ends.

Termination is automatic when no RJ-45 plug is
inserted into the socket. The absence of a mating
connector enables both termination and bias.

In rare cases, bias is unwanted, but termination is
required. To terminate the RS-485 bus, mount a
100 Ω termination resistor into an RJ-45 field
mountable connector. Then insert the connector
(with resistor) into the unused RJ-45 connector.

The RS-485 address of the inverter is unique, and defined
at the factory.

Illustration 5.14 RJ-45 Pinout Detail for RS-485

1.

GND

2.

GND

3.

RX/TX A (-)

4.

BIAS L

5.

BIAS H

6.

RX/TX B (+)

7.

Not connected

8.

Not connected

Bold = Compulsory, Cat5 cable contains all 8 wires.

For Ethernet: 10Base-TX and 100Base-TX auto cross-over.

Technical Data

L00410568-03_2q / Rev. date: 2014-06-20

47