5.4 Installation
Conditions
Parameter
Specification
Temperature
−25 °C - +60 °C (for temperature derating see the FLX Series Design Guide.)
Relative humidity
95 % (non-condensing)
Pollution degree
PD2
Environmental class according to IEC
IEC60721-3-3
3K6/3B3/3S3/3M2
Air quality - general
ISA S71.04-1985
Level G2 (at 75% RH)
Air quality - coastal, heavy industrial and agricultural zones
Must be measured and classified acc. to ISA S71.04-1985
Vibration
1G
Observe product ingress protection class
IP65
Max. operating altitude
2000 m above sea level.
PELV protection is effective up to 2000 m above sea level only.
Installation
Avoid constant stream of water.
Avoid direct sunlight.
Ensure adequate air flow.
Mount on non-flammable surface.
Mount upright on vertical surface.
Prevent dust and ammonia gases.
The FLX inverter is an outdoor unit.
Table 5.7 Conditions for Installation
Parameter
Condition
Specification
Mounting plate
Hole diameter
30 x 9 mm
Alignment
Perpendicular
±5° all angles
Table 5.8 Mounting Plate Specifications
5.4.1 France UTE Requirements
NOTICE
In France, observe the UTE C 15-712-1 and NF C 15–100
requirements.
For installation in France, apply warning label to front of
inverter.
Illustration 5.1 Warning Label